sql

Manual Motor Starter ABB 10A MS116

Rp. 100
Update Terakhir
24 Apr 2024
Pembelian Min
1 Unit

Manual Motor Starter ABB 10A MS116

The MS116-10 manual motor starter (also known as motor protection circuit breaker or manual motor protector) is a compact 45 mm width device with a rated operational current of Ie = 10.0 A. This device is used to manually switch on and off motors and to protect them reliably and without the need for a fuse from short-circuits, overload and phase failures. The manual motor starter offers a rated service short-circuit breaking capacity Ics = 50 kA at 400 VAC and trip class 10A.

  • Rated Service Short-Circuit Breaking Capacity (Ics):
    (230 V AC) 50 kA
    (400 V AC) 50 kA
    (440 V AC) 6 kA
    (500 V AC) 6 kA
    (690 V AC) 2 kA
  • Rated Ultimate Short-Circuit Breaking Capacity (Icu):
    (230 V AC) 75 kA
    (400 V AC) 75 kA
    (440 V AC) 18 kA
    (500 V AC) 15 kA
    (690 V AC) 3 kA
  • Rated Instantaneous Short-Circuit Current Setting (Ii):
    150 A
  • Setting Range:
    6.3 ... 10 A
  • Rated Operational Power AC-3 (Pe):
    (400 V) Three Phase 4 kW
  • Rated Operational Power AC-3e (Pe):
    (400 V) Three Phase 4 kW
  • Rated Operational Voltage:
    Main Circuit 690 V AC
  • Rated Operational Current (Ie):
    10 A
  • Rated Operational Current AC-3 (Ie):
    10 A
  • Rated Operational Current AC-3e (Ie):
    10 A
  • Rated Frequency (f):
    Main Circuit 50 Hz
    Main Circuit 60 Hz

Melayani penjualan dan pengiriman

JAWA BARAT, BOGOR, BANDUNG, JAKARTA, BANTEN, TANGERANG, BEKASI, JAWA TENGAH, SEMARANG, SOLO, YOGYAKARTA, JAWA TIMUR, SURABAYA, MALANG, SIDOARJO, GRESIK, MOJOKERTO, PANDAAN, BANYUWANGI, BALI, LOMBOK, BENGKULU, JAMBI, LAMPUNG, RIAU, KEP.RIAU,  ACEH,  SUMATERA BARAT, SUMATERA SELATAN, SUMATERA UTARA, BANGKA BELITUNG, KALIMANTAN BARAT, KALIMANTAN SELATAN, KALIMANTAN TENGAH, KALIMANTAN TIMUR, KALIMANTAN UTARA, SULAWESI SELATAN, SULAWESI UTARA, SULAWESI TENGGARA, SULAWESI TENGAH, GORONTALO, SULAWESI BARAT, NTT, NTB, MALUKU, MALUKU UTARA, PAPUA, PAPUA BARAT,